RT9-48V/1.4kW Rectifier Specification
Rectifier Technologies Pacific Page 4 of 6
18 Joseph Street, Blackburn North,
Victoria 3130 Australia 25/03/2010
http://www.rtp.com.au 950-1712-05 RT9 48V-1.4kW.doc
Compliances
Safety: Designed to IEC60950:1999; AS/NZS 60950:2000; UL60950:2000
EMC Emissions and Immunity: ETSI EN 300 386 V1.3.2 (2002-12)
Environmental: ETSI EN 300 019
EMC Test Levels
Emissions:
Category: Tested to comply with:
Harmonics
IEC 61000-3-2
Class A
Flicker
IEC 61000-3-3
Conducted RF
AC Terminals: CISPR 22;
DC Terminals: CISPR 22
Class B
Class A
Radiated RF
CISPR 22 Class B
Immunity
Category: Tested to comply with:
Electrostatic
Discharge (ESD)
IEC 61000-4-2
(Level 4: Air 15kV, Contact 8kV)
Criterion A
Radiated RF IEC 61000-4-3
(Level 4: 10V/m, 1kHz 80% AM)
Criterion A
Electrical Fast
Transient (EFT)
IEC 61000-4-4
(Level 4: 4kV on AC lines)
(Level 4: 4kV on DC load)
Criterion A
Criterion A
Surge
Protection
ANSI C62.41-1991 category B3 - AC lines
(Combination Wave 6kV/3kA; Ring Wave 6kV/500A)
IEC 61000-4-5 (Impulse)
(Level X: 6kV/3kA Common Mode [CM] on AC lines)
(Level X: 6kV/3kA Differential Mode [DM] on AC lines)
(Level 2: 1kV CM, 500V DM on DC lines)
IEC 61000-4-12 (Ring Wave)
(Level X: 6kV/500A, 100kHz CM & DM on AC lines)
(Level 3: 2kV CM, 1kV DM on DC lines)
Criterion B
Criterion B
Criterion B
Criterion A
Criterion B
Conducted RF
IEC 61000-4-6
(Level 3: 10V on AC, load and comms lines)
Criterion A
Voltage Dip,
Interruptions
IEC 61000-4-11
(Level: 100% dip for 10ms)
(Level: 30% dip for 500ms)
(Level: 60% dip for 1000ms)
(Level: 100% dropout for 5s)
Criterion A
Criterion A
Criterion B
Criterion B